GE IC695ETM001 Networks and Distributed I/O Systems
PACSystems RX3i Programmable Controllers
IC695HSC308
MODULE OK
PNC001
ACTIVE
USB
RESET
OK
LAN
STAT
CONFIG
TO INSTALL, TORQUE TO
6 IN LB. TO UNINSTALL,
REVERSE MOTION
IP ADDRESS
PORTS FRONT
The RX3i features a variety of communications options for distributed control and/or I/O.
Choose from Profinet Controller, Ethernet EGD, Profibus-DP, Genius and DeviceNet. These
communication modules are easy to install and quick to configure.
Networks and Distributed I/O Systems
IC695ETM001 IC695PNC001 IC695CMX128 IC695PBM300
Product Name
PACSystems RX3i Ethernet
TCP/IP 10/100Mbits, two RJ-45 ports
with built-in switch
PROFINET Controller (PNC) module,
connects a PACSystems RX3i con troller to a high-speed PROFINET
local area network. It enables the
RX3i controller to communicate
with IO-Devices on the LAN.
RX3i Control Memory Xchange
Module for Peer to Peer network.
128Megbytes of user
shared memory.
PACSystems RX3i Profibus Master
Module, Supports DPV1 Class 1
and Class 2.
Lifecycle Status Active Active Active Active
Module Type Ethernet PROFINET Controller Reflective Memory Profibus Master
Backplane Support Universal Backplane Only.
Uses PCI Bus.
Universal Backplane Only.
Uses PCI Bus.
Universal Backplane Only.
Uses PCI Bus.
Universal Backplane Only.
Uses PCI Bus.
Number of Slots Module
Occupies on Backplane 1 1 1 1
Protocol Support
SRT, Ethernet Global Data (EGD),
Channels (Client and Server),
Modbus TCP (Client and Server)
PROFINET None Required Profibus DPV1
Entity Type Client/Server Master Deterministic Peer to Peer.
Programmable Interrupt support.
Master
Communication Ports
Two RJ-45 ports one MAC Address Two RJ-45 and Two SFP Cages
(Not included, available separately).
Only one MAC address.
PROFIBUS DB-9 connector
Bus Speed
10/100Mbaud 10/100/1000Mbaud Network link speed of 2.1 Gigabits/
sec. Network transfer rate of 43
Mbyte/s (4 byte packets) to 174
Mbyte/s (64 byte packets)
12Mbaud
I/O Device Update Rate N/A Configurable: 1 ms to 512 ms
Maximum I/O Memory N/A 128 Kbytes of combined input/output
memory per PROFINET Controller
System Maximum Limits
N/A Up to 4 PNC001 per CPU
IO- Devices per I/O Controller -
64 IO-Devices per Network - 128
per network, across up to 8 I/O
controllers IO-Devices per CPU - 128
across 4 Profinet controllers Profinet
Slots per device - 256 Number of
Profinet Subslots per slot - 256 Number
of Profinet Submodules per CPU - 2048
Network Distance
Network Dependent 100 meters for cooper
Up to 70,000 meters with Fiber
Multimode Fiber up to 300 meters
between nodes. 10Km when
HUB is used
Baud Rate Dependent. Supports all
standard data rates (9.6 kBit/s, 19.2
kBit/s, 93.75 kBit/s, 187.5 kBit/s, 500
kBit/s, 1.5 MBit/s, 3 MBit/s, 6 MBit/s
and 12 MBit/s)
Bus Diagnostics
Yes Yes Network error detection. Yes, Slave Status Bit Array Table, Net work Diagnostic Counters, DP Master
Diagnostic Counters, Firmware Module
Revision, Slave Diagnostic Address
Number of Drops Supported Network Dependent 64 Drops
256 Subslots
256 Up To 125
(Requires repeater every 25 nodes)
Message Size
N/A Up to 128 Mbytes reflective memory
with parity. Dynamic packet sizes
of 4 to 64 bytes, automatically
controlled by the CMX module
244 bytes of input and 244 bytes of
output for each slave. Not to exceed
3584 bytes input and 3584 bytes
outputs total for the system.
Connector Type
Two RJ-45 Two RJ-45 and two optional SFP
plug connectors for copper or fiber
connections
Fiber optic LC type, conforms to IEC
61754-20; Zirconium ceramic ferrule;
Insertion loss 0.35 dB (maximum);
Return loss -30 dB
Profibus Connector
Internal Power Used
840 mA @ 3.3 VDC; 614 mA @ 5 VDC 3.3 V: 0.5 A with no SFP devices
installed 1.2 A maximum (two SFP
devices installed, 0.35 A per SFP
device) 5 V: 1.5 A maximum
660 mA @ +3.3 VD 253 mA @ +5 VDC 420 mA @ 5 VDC

Programmable Controllers
The RX3i features a variety of communications options for distributed control and/or I/O.
Choose from Ethernet EGD, Profibus-DP, Genius and DeviceNet. These communication
modules are easy to install and quick to configure.
Networks and Distributed I/O Systems
IC695PBS301 IC694BEM331 IC694DNM200
Product Name
PACSystems RX3i Profibus Slave Module,
Supports DPV1 Class 1 and Class 2.
PACSystems RX3i
Genius Bus Controller
PACSystems RX3i
DeviceNet Master Module
Lifecycle Status Active Active Active
Module Type Profibus Slave Genius Bus Controller DeviceNet Master
Backplane Support Universal Backplane Only.
Uses PCI Bus.
No Backplane Restrictions CPU Rack Only
Number of Slots Module
Occupies on Backplane 1 1 1
Protocol Support
Profibus DPV1 Genius DeviceNet
Entity Type Slave Master Master
Communication Ports
PROFIBUS DB-9 connector Screw Terminal Screw Terminal
Bus Speed
12Mbaud 153.6Kbaud 500Kbaud
I/O Device Update Rate
Maximum I/O Memory
System Maximum Limits
Network Distance
Baud Rate Dependent. Supports all
standard data rates (9.6 kBit/s, 19.2 kBit/s, 93.75
kBit/s, 187.5 kBit/s, 500 kBit/s,
1.5 MBit/s, 3 MBit/s, 6 MBit/s and 12 MBit/s)
7500 feet (2286 meters) at 38.4 Kbaud; 4500 feet
(1371 meters) at 76.8 Kbaud; 3500 feet (1066
meters) at 153.6 Kbaud extended; 2000 feet (609
meters) at 153.6 Kbaud standard. Maximum length
at each baud rate also depends on cable type.
500Kbaud 100 meters to 125Kbaud
500 meters. Maximum length at each baud
rate also depends on cable type.
Bus Diagnostics
Yes, Alarms Yes Yes
Number of Drops Supported
N/A 32 64
Message Size
244 bytes of input and 244 bytes of output 128 bytes 127 bytes
Connector Type
Profibus Connector Screw Terminal Screw Terminal
Internal Power Used