GE IC695LRE001 Expansion Modules for Local and Remote I/O
Programmable ControllersThe RX3i supports various expansion options for local and remote I/O to optimize
configurations. The RX3i can be expanded up to 8 expansion bases using local remote
expansion module. The RX3i also supports Ethernet remote I/O using the RX3i Ethernet
Network Interface module (IC695NKT001) Series 90-30 Ethernet Network Interface module
(IC693NIU004) for more distributed I/O.
Expansion Modules for Local and Remote I/O
IC695LRE001 IC695NKT001 IC693NIU004
Product Name
PACSystems RX3i Expansion Module PACSystems RX3i
Ethernet Remote I/O Expansion Kit.
Kit includes a NIU001 with two built-in
serial ports and ETM001
PACSystems RX3i
Ethernet Remote
I/O Expansion (Slave)
Lifecycle Status Active Active Active
Module Type High Speed Serial
Expansion Module
Ethernet Communications
(Supports redundant Ethernet modules)
Ethernet Communications
Backplane Support Universal Backplane Only Universal Backplane Only.
Uses PCI Bus.
Compatible with Series 90-30 bases only
Number of Slots Module
Occupies on Backplane No I/O slot used 3 (2 for NIU and 1 for Ethernet module) N/A
Built-in Communication Ports
N/A RJ-45 with built-in switch. 1 RS-485 port and
one RS-232 port. Supports SNP, Serial I/O,
Modbus Slave and Modbus Master N/A
I/O Discrete Points N/A 2048 Inputs/2048 Outputs maximum 2048 Inputs/2048 Outputs maximum
I/O Analog Points N/A 1264 Inputs and 512 Outputs maximum 1264 Inputs and 512 Outputs maximum
User Logic Memory N/A 5Kbytes of local logic No local logic
Network Data Rate 1 Mbaud 10/100Mbit ports (RJ-45) 10/100Mbit ports (RJ-45)
Entity Type Master Slave Slave
Network Distance Up to 700 feet (213 meters) Network Dependent Network Dependent
Bus Diagnostics Yes Supported Supported
Number of Drops Supported
Supports 7 local expansion racks.
Discrete I/O: Maximum 320 In, 320 Out,
Analog I/O: Maximum 160 In,
80 Out per base
Network Dependent
Each Ethernet NIU can also
support up to 7 additional
local I/O racks (IC694CHSxxx)
Network Dependent
Each Ethernet NIU can also
support up to 7 additional
local I/O racks (IC694CHSxxx)
Internal Power Used
132 mA @ 5 VDC 1250 mA @ 3.3 VDC; 1000 mA @ 5 VDC
for NIU controller and 840 mA @ 3.3 VDC;
614 mA @ 5 VDC for each Ethernet module
1.4 Amps @ 5 VDC